Installation Instructions38GVM / 40GVMMulti---Split High---Wall Ductless Split System38GVM --- Size 18k, 24k, 30k, 36k and 42k40GVM --- Size 9k, 12k,
10OUTDOOR UNIT INSTALLATION1. Use a rigid base to support unit in a level position.2. Locate outdoor unit and connect piping and wiring.CAUTION!EQUIPM
11GGTerminal BlockConduit panelConduitOutdoor unitCovered conduit connection for size 18k onlyL1 L2 GND L2 S L1 L2 S L1 GNDGround Ground208/230 Low V
12SYSTEM VACUUM AND CHARGEUNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage or improper operation.Never use the system co
13START--UPTest OperationPerform test operation after completing gas leak and electricalsafety check.1. Push the “ON/OFF” button on Remote Control to
14TROUBLESHOOTING38GVM Diagnostic Codes18, 24, and 30K36 and 42KIndoor UnitDisplayWiredControlIndoor and/orOutdoor UnitErrorNA Defrost Mode 1 08 NA Ou
15TROUBLESHOOTING (CONTINUED)ErrorCodeTableErrorCodeError DescriptionErrorCodeError DescriptionErrorCodeError Description13Unit A indoor pipe outlet t
16Copyright 2013 CAC / BDP S 7310 W. Morris St. S Indianapolis, IN 46231Manufacturer reserves the right to change, at any time, specifications and des
2PARTS LISTPart No. Part Name Qty1 Mounting Plate 12 Mounting Screws 53 Remote Control 14 Remote Control Holder 15 Conversion Joint Varies. See CJ Tab
3SAFETY CONSIDERATIONSInstalling, starting up, and servicing air--conditioning equipmentcan be hazardous due to system pressures, electrical component
4Refrigerant ChargeUnit SizeChargeoz. (kg.)Additional ChargeRequired After ft. (m)Additional Chargeoz./ft. (g/m)Metering Device18 K 47.6 (1.35) 20 (6.
5DIMENSIONS -- INDOORHDWA08289Unit SizeWIn. (mm)HIn. (mm)DIn. (mm)Net Operating WeightLbs. (Kg)9k 33.3 (846) 10.7 (272) 7.1 (180) 22.0 (10)12k 33.3 (8
6DIMENSIONS -- OUTDOOR (CONTINUED)35.1 (892)37.2 (946)27.6 (700)15.6 (396)13.4 (341)22.0 (560)14.5 (368)Unit: in. (mm)A12553Fig. 4 --- 38GVM024/030024
7DIMENSIONS -- OUTDOOR (CONTINUED)3.0(76)17.7 (450)3.9(99)40.0 (1015)43.4 (1103)42.8 (1087)7.5(191)24.8 (631)17.3 (440)15.8 (401)14.3 (362)4.8(121)Uni
8CLEARANCES -- OUTDOOR11.8 (300)minimumdistance fromwall11.8 (300)minimum spaceon air inlet side24.0 (610)minimum spaceon service valve side78 (2000)m
9INSTALLATION GUIDEUp to four fan coil units can be connected to one outdoor unit.Refer to the Product Data for approved combinations.Ideal installati